产品资料:
DCP102 Thermocouple LJ3
DCP103 DC (mA) LJ2
DCP104 DC (V) LJ1
3.8 SELECTION OF PRIMARY OUTPUT (OUTPUT 1) TYPE
The re quired type of Out put 1 is se lected by Link Jump ers LJ4/LJ5/LJ6/LJ7/LJ8/LJ9
on the PSU PCB (see Fig ure 3-6 and Ta ble 3-2).
3-7
Figure 3-6 PSU PCB Link Jumpers
Code Output 1 Type
PSU PCB Link
Jumper Fitted
DCP10x-1 Relay LJ5 and LJ6
DCP10x-2 DC for SSR Drive LJ4 and LJ7
DCP10x-3 DC (0 - 10V) LJ8
DCP10x-4 DC (0 - 20mA) LJ9
DCP10x-5 DC (0 - 5V) LJ8
DCP10x-7 DC (4 - 20mA) LJ9
3.9 OUTPUT 2 TYPE/OUTPUT 3 TYPE
The type of output for Output 2 and Output 3 is determined by the Option PCB
fitted in the appropriate position (see Figure 3-1) and, in the case of the DC
Output Option PCB being fitted, the setting of Link Jumpers LJ8 and LJ9 on that
Option PCB (see Figure 3-7 and Table 3-3). There are three types of option PCB
which may be used for Output 2 and Output 3:
1. Re lay Out put Op tion PCB (no link jump ers)
2. SSR Out put Op tion PCB (no link jump ers)
3. DC Out put Op tion PCB (link jump ers as shown in Fig ure 3-7)
3-8
Figure 3-7 DC Output Option PCB (Output 2/Output 3)
Output 2 Output 3
Code Output Type
Link Jumpers
Fitted
Code Output Type
Link Jumpers
Fitted
DCP10x-x-3 DC (0 - 10V) LJ8 DCP10x-x-x-3 DC (0 - 10V) LJ8
DCP10x-x-4 DC (0 - 20mA) LJ9 DCP10x-x-x-4 DC (0 - 20mA) LJ9
DCP10x-x-5 DC (0 - 5V) LJ8 DCP10x-x-x-5 DC (0 - 5V) LJ8
DCP10x-x-7 DC (4 - 20mA) LJ9 DCP10x-x-x-7 DC (4 - 20mA) LJ9
4 CONFIGURATION MODE
4.1 ENTRY INTO CONFIGURATION MODE
To enter Configuration Mode:
1. Ensure that the Digital Controller Programmer is powered-down.
2. Power-up the Digital Controller Programmer and, within 30 seconds of
|