The desired setting can be achieved using the Up/Down keys. If the External
Option parameter has not been set to inP or both, pressing the SET UP key will
return to the initial External Option parameter display. If the External Option
parameter has been set to either inP or both, pressing the SET UP key will
change the Message Display to:
and the lower main display to one of:
The desired setting can be achieved using the Up/Down keys. Pressing the SET
UP key will then return to the initial External Option parameter display. The digital
inputs are used to select a program to run, as follows:
4-3Digital Inputs = TTL Level Digital Inputs = Contacts (Switches)
Digital Inputs Program
Selected
Digital Inputs Program
R0 R1 R2 R0 R1 R2 Selected
0 0 0 Program 1 Closed Open Open Program 1
1 0 0 Program 2 Open Closed Open Program 2
0 1 0 Program 3 Closed Closed Open Program 3
1 1 0 Program 4 Open Open Closed Program 4
0 0 1 Program 5 Closed Open Closed Program 5
1 0 1 Program 6 Open Closed Closed Program 6
0 1 1 Program 7 Closed Closed Closed Program 7
1 1 1 Program 8 Open Open Open Program 8
To exit from the Hardware Definition Code facility, press the Down and SET UP
keys simultaneously (which will cause a return to the normal Configuration Mode).
Alternatively, either of the methods of exit from Configuration Mode (see
Subsection 4.5) may be used here.
4.3 CONFIGURATION MODE PARAMETERS
The Configuration Mode parameters are presented for view/edit in the following
sequence:
Parameter
Message
Display
Function Available Settings/values
(Lower Main Display)
Primary
Input
Range 1
Code displayed
defines input
type/range (see
Appendix A).
See Appendix A.
Control
Action
|