详细介绍:
HONEYWELL温控器DC1040CT-101100-E说明书
联系人:魏工 电话:15882174684
座机:028-84472033
QQ:2030149354
产品资料:
0 (OFF) - 99 min 59 s.
Manual Reset (Bias): Added each control algorithm execution.
Adjustable in the range 0 - 100% of output
power (single output) or –100% to +100%
of output power (dual output).
Deadband/Overlap: –20% to +20% of Proportional Band 1 +
Proportional Band 2.
ON/OFF Differential: 0.1% to 10.0% of input span.
Auto/Manual Control: User-selectable with “bumpless” transfer
into and out of Manual Control.
Cycle Times: Selectable from 0.5secs to 512 secs in
binary steps.
Setpoint Range: Limited by Setpoint Maximum and Setpoint
Minimum.
Setpoint Maximum: Limited by Setpoint and Range Maximum.
Setpoint Minimum: Limited by Range Minimum and Setpoint.
Setpoint Ramp: Ramp rate selectable 1 - 9999 LSDs per
hour and infinite. Number displayed is
decimal-point-aligned with selected
range.
ALARM CON TROL
Maximum Number of
Alarms:
Two “soft” alarms plus Loop Alarm
Max. No. of Outputs
Available:
Up to two outputs can be utilised for alarm
purposes.
Combinatorial Alarms: Logical OR or AND of alarms to an
individual hardware output is available.
PRO GRAM FA CILI TIES
Programs (profiles): Eight, each with free-form segments
Length of Program: Adjustable in the range 1 to 16 segments;
programs cascadable - maximum length
121 segments
Segment Types: Ramp, Soak, Join, Repeat or End
Program Cycling: Range 1 to 9999, infinite
B-6Delayed Start: May be set in the range 0 to 99:59
(hours:min utes). One set ting ap plies to all
pro grams
Control: Run, Hold, Abort, x60 (local or remote)
Select Program (local or remote)
Jump to next segment.
Start From: Either current process variable value or
|