详细介绍:
霍尼韦尔DC1040CR-101100-E辽宁一级代理商
联系人:魏工 电话:15882174684
座机:028-84472033
QQ:2030149354
产品资料:
20 - 50V AC 50/60Hz or 22 - 65V DC
(option)
B-10Source Resistance: 1000W maximum (thermocouple)
Lead Resistance: 50W per lead maximum balanced (Pt100)
Per form ance Un der Op er at ing Con di tions
Temperature Stability: 0.01% of span/oC change in ambient
temp.
Cold Junction
Compensation
(thermocouple only):
Better than ±1oC.
Supply Voltage Influence: Negligible.
Relative Humidity
Influence:
Negligible
Sensor Resistance
Influence:
Thermocouple 100W: <0.1% of span error
Thermocouple 1000W: <0.5% of span error
RTD Pt100 50W/lead: <0.5% of span error
Radiated RF Field
Influence:
Degradation of Output 1 accuracy to 3%
at spot frequencies in the range 80 -
350MHz at field strength of 10V/m.
EN VI RON MEN TAL
Operating Conditions: See PERFORMANCE.
EMI Susceptibility: Designed to meet EN50082-1:1992 and
EN50082-2:1995.
EMI Emissions: Designed to meet EN50081-1:1992 and
EN50081-2:1994.
Safety Considerations: Designed to comply with EN 61010-1:1993.
Supply Voltage: 90 - 264V AC 50/60Hz (standard)
20 - 50V AC 50/60Hz or 22 - 65V DC
(option)
Power Consumption: 4 watts approximately.
Front Panel Sealing: To IP65.
B-11PHYSI CAL
Dimensions: Depth - 100mm approximately
Front Panel:
Width - 96mm, Height - 96mm (1
4-DIN)
Mounting: Plug-in with panel mounting fixing strap.
Panel cut-out 92mm x 92mm.
|