User must reconfigure all required settings before using the instrument in a live 

application.

Automatic Tuning Menu

The Automatic Tune Menu is used engage the Pre-tune and/or Self-tune facilities to assist 

the user in setting up Proportional band(s), Integral and Derivative parameter values.

Pre-tune can be used to set PID parameters approximately. Self-tune may then be used to 

optimise the tuning if required.

Pre-tune can be set to run automatically after every power-up by enabling Auto Pre-Tune.

The TUNE indicator (LED 3)* will flash while pre-tune is operating, and is continuously on 

whilst Self-tune is operating. If both Pre-tune and Self-tune are engaged the AT indicator will 

flash until Pre-tune is finished, and is then continuously on.

Note:

Self-Tune will not engage if either primary or secondary control outputs are set for On-Off 

control.

Pre-Tune will not engage if either primary or secondary control outputs are set for On-Off 

control, during setpoint ramping, if a profile is running or if the process variable is less than 

5% of the input span from the setpoint.

Navigating Automatic Tuning Menu

Press to move forward or to move backwards through the selections.

Press or to engage or disengage the tuning as required.

Hold down Dand press Cto return to the Main Menu

Scrolling Help Text” is shown at the bottom of the screens to aid navigation.

*Provided the function of LED3 has not been changed (LED functions can be altered using 

the PC Configuration Software).

Table 19. Automatic Tuning Menus Screens

Ï Automatic Tuning Menu:

Automatic Tuning Mode 

Unlocking

Enter correct code number to access the Automatic Tuning Menu.

Pre-Tune w Turns Pre-Tune on/off. Pre-Tune is disabled in On-Off Control Mode; 

if the PV is less than 5% of span from SP; during Profiles or if the 

Setpoint is Ramping.

Pre-Tune Status Shows the current Pre-Tune status. Active or Inactive.

Self-Tune Turns Self-Tune on/off. Self-Tune is disabled in On-Off Control 

Mode.

Self-Tune Status Shows current Self-Tune status. Active or Inactive.

Auto Pre-Tune Enable Enables/Disables Automatic Pre-Tune. When enabled, this attempts 

to perform a Pre-Tune at every power-up. Normal Pre-Tune 

engagement rules are applied (see Pre-Tune above)

Profiler Setup Menu

Refer to the Profiler Option section of this manual for more details about the profiler features.

Screens marked º will not time-out automatically. They must be completed for a valid profile 

to be created.

Table 20. Profiler Setup Menu Screens

 