Segment Dwell 

Time

º The time (hh:mm:ss) to maintain the current setpoint if the segment 

type is Dwell.

Profile Header: Settings that apply to the chosen profile as a whole

Enter Profile Name º Up to 16 characters can be used to name each profile

Profile Starting 

Point

º The setpoint value to be used at the beginning of the first segment. 

From: Actual Setpoint or Process Variable value at the time the 

profile starts.

Profile Start 

Trigger

º From: None (profile start is not delayed); After Delay or Day and 

Time (Recorder version only).

Profile Start Time º The time (hh:mm:ss) when the profile should run. – This applies only 

if Day and Time is the Profile Start Trigger. Caution: Take care not 

to clash with other profiles. A Profile cannot start if another is 

running.

Profile Start Day(s) º The Day(s) when the profile should run. From: Mon; Tue; Wed; Thu; 

Fri; Sat; Sun; Mon-Fri; Mon-Sat; Sat-Sun or All. – This applies only if 

Day and Time is the Profile Start Trigger.

Profile Start Delay º The delay time, up to 99:59 (hh:mm), for a profile to begin after the 

start request has been given.

Profile Recovery 

Method

º The power-on action if profile was running at power-down (e.g. after 

a power cut), or following correction of a signal break. From: Control 

outputs off; Restart profile from the beginning; Maintain last profile 

setpoint; Use controller setpoint; Continue profile from where it was 

when power failed.

Profile Recovery 

Time

º The Recovery Method is ignored (the profile continues from where 

power failed), if power off for less than this time. Max 99:59 

(hh:mm). - Recorder version only.

Profile Abort 

Action

º Action after profile has been forced to stop before its end. From:

Control outputs off; Maintain last profile setpoint or Use controller 

setpoint.

Profile Cycles º The number of times the program should run each time it is started 

(1-9999 or Infinite).